AirSelect3D Blog
Plate HRS Frost Protection: Preheat vs Bypass vs Modulation
Full bypass is the cheapest frost protection to buy and the most expensive to run: at -12 °C outdoor with a 75 %-efficient counter-flow plate, bypassing throws away roughly 43 kW of recovery on a 5 000 m³/h unit, while a preheat coil holding the exchanger frost-free costs about 12 kW. That factor-of-three gap is decided at selection time, in a dialog most quotes click through in two seconds.
Why plate exchangers frost, and at what temperature
Frost forms on the extract side, not the intake side. Room air at 22 °C / 35 % RH has a dewpoint near 6 °C. As it gives up heat to the incoming outdoor air it drops below that dewpoint, condenses on the plates, and once the local plate surface falls below 0 °C the condensate freezes. Ice narrows the exhaust channels, pressure drop climbs, efficiency collapses, and eventually the exhaust fan stalls against its own curve.
The counter-intuitive part: the more efficient the exchanger, the earlier it frosts. A high-efficiency counter-flow core drives the exhaust air closest to the intake temperature, so its coldest corner reaches 0 °C sooner.
| Core type | Typical dry efficiency | Typical frost onset (22 °C / 35 % RH extract) |
|---|---|---|
| Cross-flow plate | 50-65 % | around -8 to -12 °C outdoor |
| Counter-flow plate | 70-85 % | around -3 to -6 °C outdoor |
| Rotary wheel | 70-85 % | several K lower; speed modulation usually suffices |
Onset figures are indicative — manufacturers publish a frost-free limit per core, and it shifts with extract humidity. A humidified hospital or pool extract at 50 % RH frosts several kelvin earlier than a dry office. Always read the limit against the project's extract condition, not the catalogue's.
The three strategies, priced
Take a 5 000 m³/h unit (1.67 kg/s, ~1.68 kW/K), 75 % counter-flow core, 22 °C extract, 20 °C supply target, at an outdoor design point of -12 °C.
| Strategy | What it does | Heat input at -12 °C | Notes |
|---|---|---|---|
| Full bypass | Damper routes 100 % of outdoor air around the core below a setpoint | ~54 kW in the heating coil | Zero recovery exactly when the load peaks |
| Preheat coil | Lifts intake from -12 °C to -5 °C before the core | ~12 kW preheat + ~8 kW reheat ≈ 20 kW | Adds 30-60 Pa air-side, all year |
| Modulating bypass | Bypasses only the fraction needed to hold the exhaust above 0 °C | ~24 kW at 30 % bypass | No extra coil, no extra pressure drop |
The ranking at design conditions is clear, but design conditions occur for a handful of hours. Over a season the picture flattens: in a maritime climate that drops below -5 °C for 100-200 hours a year, the preheat coil's permanent SFP penalty can eat most of the recovery it saves. In a continental climate with 800+ hours below -5 °C, it pays back several times over.
Two corrections engineers routinely skip:
- Compare energy carriers, not kilowatts. An electric preheat coil at €0.22/kWh against gas-fired reheat at €0.08/kWh reverses the arithmetic above. Price the strategy, don't just count kW.
- Charge the preheat coil its fan energy. 40 Pa across both a supply-side coil and its 8 760 hours of operation is a real number in the SFP_int budget, and it counts in every season — including the summer case where the coil does nothing at all.
Control: setpoint or pressure?
Frost control is triggered one of two ways. Temperature-based control acts on an exhaust-outlet or intake sensor crossing a fixed setpoint — simple, robust, and systematically conservative, because the setpoint has to cover the worst extract humidity the building will ever see. Differential-pressure-based control watches Δp across the exhaust side of the core and reacts to actual ice, not to a proxy for it. It runs the exchanger closer to the real limit and typically recovers meaningfully more over a heating season, at the cost of one sensor and a properly commissioned threshold.
A fourth strategy exists — unbalancing the fans, reducing supply flow so the warmer extract stream defrosts the core. It is common in residential heat-recovery units and unacceptable in most commercial work: it depressurises the building, breaks the balanced-flow assumption behind the EN 308 efficiency figure, and invalidates the airflow the room loads were sized on.
Note also that ErP Regulation 1253/2014 already requires a thermal bypass facility on non-residential ventilation units fitted with heat recovery, for summer free cooling. The hardware is therefore usually present anyway — which is exactly why "bypass" gets selected as the frost strategy by default rather than by analysis.
What to check before you sign the selection
- What frost-free limit does the core carry at the project's extract temperature and humidity, not the catalogue's dry test point?
- How many hours per year does the site actually spend below that limit? That single number decides preheat vs bypass.
- Is the preheat coil's pressure drop already inside the quoted SFP, or was SFP taken from a bypass-only configuration?
- Does the frost strategy change the winter Eurovent class? It usually does — see why units pass in January and fail in July.
- If cross-contamination is not a constraint, has a rotary wheel been priced against the plate + preheat combination? Speed modulation is often the cheapest frost strategy of all.
Where the tooling matters
AirSelect3D carries the frost strategy as part of the HRS selection, so a preheat coil's air-side pressure drop flows straight into SFP_int and the ECP-05-2026 class calculation instead of being remembered later — and switching from bypass to preheat recalculates the whole psychrometric chain and both seasonal classes in the same pass.
Design your next AHU in 3D — in five minutes.
AirSelect3D runs certified manufacturer engines (Camfil, Ziehl-Abegg, eBM Papst, Friterm, Hoval) and ships an ErP-compliant Eurovent dossier with every selection.
Launch the 3D Designer →